Solar Calculator for Lagos — Size Am From Your Load

Daily kWh → panel, battery, inverter · 4.5 peak sun hours · price from live component data

Plenty Lagos solar quote dey start from the wrong side — installer go ask your budget, then size system to match am. Na backwards. Sizing suppose start from your load: wetin you dey actually run, for how many hours, and how much of am must work when light go. Once you sabi that, you fit judge any quote for like one minute.

CALCULATOR

Size your system from your load

Set how many of each one you dey run and for how many hours per day.

LED bulb
10W
Standing fan
75W
Fridge / freezer
150W
TV + decoder
120W
Wi-Fi router
15W
Laptop / phone charging
70W
Water pump (1HP)
750W
AC (1.5HP inverter)
1000W
Energy wey you dey use per day6.5 kWh
Panel array wey you need1.9 kW
Panel (450W each)5
Battery wey you fit use3.8 kWh
Inverter rating1 kVA
Panel cost (equipment alone)₦475.0K–₦650.0K

The sizing dey assume Lagos average of 4.5 peak sun hours, 25% system loss and 85% usable depth of discharge for lithium. The cost na equipment alone — labour and wiring dey usually add 10–20% on top. Na planning estimate to check quote with, no be quote.

HOW SIZING DEY WORK

Start from your daily kWh, no be your budget

Add each appliance watt times the hours wey you dey run am per day, then divide by 1,000. Fridge wey be 150W wey dey run 24 hours na 3.6kWh. Six bulb of 10W for six hours na 0.36kWh. Pressing iron of 1,000W for 20 minutes na 0.33kWh. Plenty Lagos flat wey no dey run AC dey land between 3kWh and 8kWh per day; add just one 1.5HP AC wey run six hours, e go add like 6kWh by itself.

That daily kWh na the one number wey any correct installer go ask you. If quote land and nobody ask wetin you dey run, dem size the system to your pocket, no be your house — so e go either too big (you overpay) or too small (e go cut for night, wey be the exact time you want am).

Na sun hours dey size panel, no be watt alone

Lagos dey average like 4.5 peak sun hours per day. Na that number dey turn panel rating into real energy: 450W panel no dey make 450W all day — e dey make like 450W × 4.5 hours ≈ 2kWh for better day, and less well well for July–September rain. So to cover 6kWh daily load, na like 6 ÷ 2 = 3 panel for theory, but for real life na 4–5 once you add cloud, dust for the glass, and charging loss.

Na why panel count be the part of quote wey you suppose check pass. To reduce panel na the cheapest way for installer to hit sweet price, and you no go see am until the first cloudy week, when battery no go full again and the system go quietly start to lean on NEPA.

Na battery dey decide how blackout go feel

Panel only dey work while sun dey, so every hour of night backup dey come from battery. Size am by the load wey you need after dark, no be your total daily load — for most house na fridge, fan, light, phone and router, wey small pass the daytime peak. Then add headroom: lithium (LiFePO4) battery dey usually rated for like 80–90% usable depth of discharge, but tubular lead-acid no suppose go below like 50% if you want am last the years wey dem talk.

Na that depth-of-discharge difference make 5kWh lithium and 5kWh tubular no be the same buy. Lithium go give you like 4–4.5kWh wey you fit really use; tubular go give you like 2.5kWh before you start to cut im life short. Compare usable kWh, no be the kWh wey dem write for body, if not the cheaper one go look like better deal pass wetin e be.

RELATED
FULL PACKAGE
Installed package price and payback

The tier price na fully installed — panel, inverter, battery and labour join.

PANEL PRICE
Wetin panel dey cost for Lagos

Price per watt across size, with source and the date wey dem verify am.

QUESTIONS WEY DEY ASK

Sizing question

Na your daily kWh dey set panel count, no be the inverter rating. But normally, 5kVA hybrid inverter dey pair with like 3–5kW of panel, wey be like 7–11 panel if each one na 450W. If e less pass that, the inverter no go ever reach im rating; if e plenty pass, you dey pay for capacity wey the inverter no fit convert at once.